Arc Fault Protection on Navy Ships:

 

In the late 1970s the Navy recognized that electrical fires were becoming a major problem in submarines. About three fires per year were occurring in the main electrical distribution switchboards across the submarine fleet. Those fires have had a major impact on mission readiness and could potentially cause loss of life and ship. In three-quarters of a second, the current from the smallest generator can burn a fist-sized hole in the side of a switchboard. The damage initially increases exponentially with time, limited only by available current from the generators. Figure 1, a photograph from an older SSN 637 class submarine, shows extensive damage from a typical electrical fire.

 

Figure 1. Damage from an arc-generated electrical fire.

 

Main submarine electrical switchboards conduct thousands of amps over bare copper bus bar 1–12 inches wide and 0.25–1 inch thick. On each ship, 15 to over 100 of these switchboards exist. Large circuit breakers control the flow of current to remote loads and smaller switchboards. An arc of several hundred amps can exist and not cause a breaker to open since normal loads draw much more current. The arc is not a short across the circuit, but a resistive load yielding heat; therefore, the breakers do not open. Faulty connections due to corrosion, faulty initial fastening, vibration, etc., cause 60–80% of arcs. Contamination and foreign objects also cause arcs.

In 1979 the submarine force became aware that JHU/APL had considerable experience in the creation and control of large power electrical arcs for heating air that was used in aerothermal testing at the Avery Advanced Technology Development Laboratory, now part of the Research and Technology Development Center. The Arc Fault Detection (AFD) Program at APL began by setting up an arc test facility to create and control reproducible arcs representative of those on the ships. Many different types of measurements were made to determine which sensing technique detected best, responded fastest, ignored the background best, would be least invasive, and could be mass-produced at the least expense. Air temperature is a reliable detector but responds too slowly. Conducted electromagnetic interference emissions identify an arc but do not localize the source well enough. Current, voltage, sound, infrared, radiated electrical emissions, and magnetic fields were tried and discarded. Finally, optical signals were tried until a band in the ultraviolet with satisfactory discrimination was identified; in addition, pressure was found to be a second good indicator. Tests were conducted to determine optimal operating parameters, and sensors were developed around those signals (see Fig. 2). Cost, performance, reliability, and maintainability were the drivers.

Figure 2. An arc and submarine arc fault detector components.

 

APL took the arc problem from research and development to sensor development and into system development. Level 3 production drawings were created and delivered to the Navy, and systems were mass-produced after competitive bid. The first AFD systems were designed for the older SSN 637 class submarines. APL has now designed systems for all classes of submarines. More than 10,000 photosensors, 4,000 pressure sensors, and 175 control units have been built and deployed on all classes of submarines.

In AFD-protected submarine switchboards, the photosensor portion of the sensor contains a narrow-band ultraviolet filter and LEDs inside a hermetically sealed photodetector. During built-in-test, the light from the LEDs is bounced from the back of the filter into the photodiode for an end-to-end test of the sensor. Once a full power arc is created, the air within the switchboard is rapidly heated and the vents cannot relieve the pressure wave. A high-speed pressure switch closes if the pressure inside the switchboard exceeds that outside the enclosure. Solid-state switches inside the pressure transducer housing allow an end-to-end test to be conducted when the central control unit performs the built-in-test.

Breakers that can cut off the flow of current to the AFD-protected switchboards are identified upstream of the protected switchboards. Because many switchboards have common feeds, removing power from one entails removing power from several. Since the operation of almost everything on a submarine depends on electricity, zones of protection are defined to allow any switchboard sustaining an arc to be isolated so that a minimum of other switchboards are affected.

A control unit receives signals from the sensors and performs additional processing. When a valid arc is recognized, the appropriate breakers are tripped. If the breakers are tripped within less than 0.25 second, the damage will be limited to smoke damage and major repairs will not be needed. More than 2000 arcs between a few kilowatts and several megawatts were created to design and test the AFD system.

Figure 1 shows that substantial pieces of copper bus are missing and that holes were blown through the switchboard cover. Figure 3 shows that only light smoke damage was sustained in a protected ship. The AFD system has now accumulated over 400 ship years of operation without a single erroneous operation. It has correctly detected and protected against six electrical fires since the first installation in 1993.

Figure 3. Minimal damage from an electrical arc in a protected circuit.

As part of the effort to design an AFD system for the New Attack Submarine (NSSN), the Navy asked APL to increase the performance of the system and to find ways of predicting imminent arcs. The photosensor design was simplified, and its performance and life span were increased. The production cost was reduced from $2500 to $600 per sensor, resulting in a projected life cycle cost savings of $55 million in procurement costs.

As a part of the NSSN design, a thermal ionization detector was developed to detect small particles released into the air from overheated cables or from Glyptal-coated bus bar junctions. Overheated insulation is detected at 200–300°C, well below the 1083°C needed to melt copper and cause an arc. With this innovation, the AFD system becomes a Continuous Thermal Monitoring (CTM) System, which can predict most arcs in time to prevent them from happening.

Currently, the AFD/CTM effort is toward redesigning the system for use on nuclear aircraft carriers. Because of the Navy’s new design thrust, APL is making a major effort to reduce cost, including using commercial off-the-shelf assemblies and parts rather than the historical full MIL-SPEC design requirements. The new AFD/CTM system design uses a star wiring that serves individual sensors on a network-based system with remote intelligent sensor interface modules. Commercial enclosures (Fig. 4) and plastic sensor housings are used. The original Trident AFD hardware cost $26,600 per protected ­switchboard. Through innovative design, the nuclear aircraft carrier AFD/CTM design is projected to cost $4,500 per switchboard despite having many new features. The current and future AFD systems should be able to be used in a wide range of applications.



 

Figure 4. Carrier arc fault detector control unit.

H. Bruce Land, III, RAS, 240-228-6083

Acknowledgements.  This program is sponsored by D. E. Strawser, SEA 03Z44. H. B. Land (RAS) is the program manager.

 



Home - in new window

Usefull Links - Search Engines - Related Sites